What Size Heat Pump Does My Business Need? Including Cascade Systems

The right heat pump size for a business comes from a room-by-room heat loss calculation, which gives the building’s peak heat demand in kW. The heat pump’s output at its design flow temperature then needs to match or exceed that figure, and floor area alone is not a reliable guide. Where one unit cannot cover the demand, larger buildings link several heat pumps together in a cascade.

We survey and size commercial heat pumps for businesses, schools, care homes and public buildings across Hinckley, Leicester, Coventry, Nuneaton, Tamworth and Rugby. Every job starts with a site survey, because two buildings of the same size can need very different heat pumps, and we install cascade systems regularly, including at Myton care home.

How Is the Right Heat Pump Size Worked Out?

A heat loss calculation adds up the heat the building loses through its walls, floors, roof, windows and doors, plus the heat lost through ventilation, on the coldest day expected for its location. It is worked out room by room, which also sets the size of the radiators, underfloor heating or fan convectors in each space.

An EPC is not a substitute. The MCS has made clear that the calculation used for an EPC is not the same as a heat loss calculation and is not accurate enough for sizing a heat pump.

Heat pump output falls as the flow temperature rises, so the capacity has to be checked at the temperature the system will actually run at, and the emitters sized for that same temperature.

What Information Does a Heat Pump Sizing Survey Need?

  • Building plans and measurements
  • The area of walls, floors, roof, windows and doors
  • The thermal performance (U-values) of each, including any insulation
  • The location, which sets the design temperature
  • Hot water demand, such as showers, kitchens and washrooms
  • Opening hours and occupancy
  • The existing heating system and its radiators or pipework

Where a building is poorly insulated, it is usually worth improving the insulation first, which lowers the heat demand and the size of the heat pump needed.

What Happens If a Heat Pump Is the Wrong Size?

Both undersizing and oversizing cause problems. The building may not reach a comfortable temperature, running costs rise, and the unit can be prone to faults over time.

When Does a Business Need More Than One Heat Pump?

As the heat demand of a building grows, a single unit may not be enough, or may be impractical to fit. Larger sites then link several heat pumps so they share the load. Care homes, schools and leisure centres often work this way.

What Is a Cascade Heat Pump System?

In a cascade, two or more heat pumps work together through one controller, and extra units switch on as demand rises and drop out when it falls. As an illustration, a building needing around 100kW in winter but only about 40kW in summer could use two 50kW units. Both run when demand is above 50kW, and in summer only one runs.

Linked units can also have different jobs. One or more can produce hot water while the others handle space heating, and where a building has circuits running at different temperatures, separate units can each be set up for their own circuit.

Why Would a Care Home or Large Building Use Several Heat Pumps?

  • Resilience. If one unit fails, the others keep running. They may not meet the full load, but the building keeps some heat until the unit is repaired, and engineers can service one unit while the rest stay on. That matters in buildings that cannot be left without heating, such as care homes.
  • Matching the seasons. Units come on only when needed, so the system produces just the heat the building asks for.
  • Separate duties. Hot water and heating can be handled by different units set up for different temperatures.
  • Scale. A single unit large enough for a big building can be impractical, while several smaller units are easier to fit and phase.

How Do Linked Heat Pumps Share the Heating Load?

The units switch on and off as demand changes. Because heat pumps work best on long, steady run cycles, a cascade lets units run for long periods, with one covering hot water while another handles heating.

Flow temperature matters here too. A heat pump becomes less efficient as the temperature it has to deliver rises. One manufacturer gives an example where the coefficient of performance falls from 3.75 to 2.25 as the output temperature rises. That is why a heat pump cascade should be designed for the lowest flow temperature the building can use, with emitters sized to suit.

How Is a Heat Pump Cascade Different From a Boiler Cascade?

A boiler cascade links several boilers to share the load, which improves resilience and lets the system adjust to changing demand. Boiler cascades normally run at the highest temperature the building needs and mix it down where a lower temperature is wanted. A heat pump cascade should not be run at a single high temperature in the same way.

The two can also be combined, with boilers and heat pumps working together under a hybrid controller. For typical costs of multi-boiler plant rooms, see our guide to commercial boiler replacement cost, and for boiler work, our commercial boiler installation service.

What Does a Cascade System Need in the Plant Room?

The units are normally grouped in one central plant room, so the room needs space for each unit, the pipework between them, hot water storage and access for servicing. Ground source cascades also need a ground array sized for the building’s whole heat demand. We plan the layout during the survey so one unit can be serviced without shutting down the rest.

How Much Does a Commercial Heat Pump Cost?

Cost follows size, so it is worth seeing what published figures look like. One UK guide gives these ranges, before any grants:

Heat demandTypical installed costTypical premises
10 to 15kW£12,000 to £18,000Small offices and SMEs
30 to 50kW£30,000 to £55,000Pubs, restaurants and town halls
100kW and above£95,000 to £148,000Schools and leisure centres, often multi-unit cascades

These are published figures, not our quotes, and the source does not say whether VAT is included. Hot water storage, pipework and radiator upgrades can move the price a long way. Grants may be available for some smaller premises, and our guide to the Boiler Upgrade Scheme explains how the scheme works. For a quote based on your building, see our commercial heat pumps page.